Detail Fluke 1625 GEO Earth Ground Testers
Fluke 1625 GEO Earth Ground Testers
RA 3-pole ground resistance measurement ( IEC 1557-5)
Measuring Voltage
Fluke 1623 Vm = 48 V ac
Fluke 1625 Vm = 20/ 48 V ac
Short circuit current
Fluke 1623 > 50 mA
Fluke 1625 250 mA ac
Measure frequency
Fluke 1623 128 Hz
Fluke 1625 94, 105, 111, 128Hz
Resolution
Fluke 1623 0.001 & to 10 &
Fluke 1625 0.001 & to 100 &
Measuring range
Fluke 1623 0.001 & to 19.99 k&
Fluke 1625 0.001 & to 299.9 k&
Intrinsic error
Fluke 1623 ± ( 2 % of reading + 3 digit)
Fluke 1625 ± ( 2 % of reading + 2 d)
Operating error
Fluke 1623 ± ( 5 % of reading + 3 d)
Fluke 1625 ± ( 5 % of reading + 5 d)
RA 4-pole ground resistance measurement ( IEC 1557-5)
Measuring Voltage
Fluke 1623 Vm = 48 V ac
Fluke 1625 Vm = 20/ 48 V ac
Short circuit current
Fluke 1623 > 50 mA
Fluke 1625 250 mA ac
Measure frequency
Fluke 1623 128 Hz
Fluke 1625 94, 105, 111, 128Hz
Resolution
Fluke 1623 0.001 & to 10 &
Fluke 1625 0.001 & to 100 &
Measuring range
Fluke 1623 0.001 & to 19.99 k&
Fluke 1625 0.001 & to 299.9 k&
Intrinsic error
Fluke 1623 ± ( 2 % of reading + 3 d)
Fluke 1625 ± ( 2 % of reading + 2 d)
Operating error
Fluke 1623 ± ( 5 % of reading + 3 d)
Fluke 1625 ± ( 5 % of reading + 5 d)
RA 3-pole ground resistance measurement with current clamp
Measuring Voltage
Fluke 1623 Vm = 48 V ac
Fluke 1625 Vm = 20/ 48 V ac
Short circuit current
Fluke 1623 > 50 mA
Fluke 1625 250 mA ac
Measure frequency
Fluke 1623 128 Hz
Fluke 1625 94, 105, 111, 128Hz
Resolution
Fluke 1623 0.001 & to 10 &
Fluke 1625 0.001 & to 10 &
Measuring range
Fluke 1623 0.001 & to 19.99 k&
Fluke 1625 0.001 & to 29.99 k&
Intrinsic error
Fluke 1623 ± ( 7 % of reading + 3 d)
Fluke 1625 ± ( 7 % of reading + 2 d)
Operating error
Fluke 1623 ± ( 10 % of reading + 5 d)
Fluke 1625 ± ( 10 % of reading + 5 d)
RA 4-pole selective ground resistance measurement with current clamp
Measuring Voltage
Fluke 1623 Vm = 48 V ac
Fluke 1625 Vm = 20/ 48 V ac
Short circuit current
Fluke 1623 > 50 mA
Fluke 1625 250 mA ac
Measure frequency
Fluke 1623 128 Hz
Fluke 1625 94, 105, 111, 128Hz
Resolution
Fluke 1623 0.001 & to 10 &
Fluke 1625 0.001 & to 10 &
Measuring range
Fluke 1623 0.001 & to 19.99 k&
Fluke 1625 0.001 & to 29.99 k&
Intrinsic error
Fluke 1623 ± ( 7 % of reading + 3 d)
Fluke 1625 ± ( 7 % of reading + 2 d)
Operating error
Fluke 1623 ± ( 10 % of reading + 5 d)
Fluke 1625 ± ( 10 % of reading + 5 d)
Stakeless ground loop measurement
Measuring Voltage
Fluke 1623 Vm = 48 V ac
Fluke 1625 Vm = 20/ 48 V ac
Measure frequency
Fluke 1623 128 Hz ( 125 Hz on request)
Fluke 1625 94, 105, 111, 128Hz
Noise current ( Iext)
Fluke 1623 Max. Iext = 10 A ( ac) ( RA < 20 & )
Max. Iext = 2 A ( ac) ( RA 3000 measurements
Fluke 1625 Typical 3000 measurements ( RE+ RH d 1 k& )
Typical 6000 measurements ( RE+ RH d 10 k& )